ADV200 • Quick start up guide 41
5.1.12 Connection of fans
Sizes
1007 ... 61320
No connection is necessary: the drive’s internal power supply unit powers the fan (+24Vac).
Version before 2009/125/CE (ErP regulation)
Terminals U3 V3 PE 31 32
Sizes
71600 ... 72500
400 kW
(1)
500 kW (1)
1 x 230V (±10%)
50/60Hz,
2.4A (50Hz) - 3.3A
(60Hz)
Ground
250V/10A contact
OK fan contact management terminals 31-32:
Closed: Internal fan
OK
and powered;
Open: Internal fan in over temperature alarm and/or input power supply
not available.
Power the internal fan (max 600W) with a single-phase voltage on terminals U3/V3.
Type of fan compliant 2009/125/CE (ErP)
ADV200 starting from S/N 33GC017331
U3 V3 W3 PE 31 32
3 x 400V (±10%)
50/60Hz,
1.25/1.65Arms
3 x 460V (±10%)
60Hz, 1.55Arms
Ground
250V/2A contact
OK fan contact management terminals 31-32:
Closed: Internal fan OK (also with non-powered fan)
Open: Internal fan in over temperature alarm
Power the internal fan ( 570W @400V, 930W @460V ) with a three-phase voltage on terminals U3/V3/W3.
Version before 2009/125/CE (ErP regulation)
Terminals U3 V3 W3 PE 31 32
Sizes
73150 ... 73551
630 kW
(1)
710 kW (1)
900 kW (1)
1 MW (1)
3 x 400V (±10%)
50Hz, 1,55Arms
or
3 x 460V (±10%)
60Hz, 1,7Arms (2)
Ground
250V/10A contact
OK fan contact management terminals 31-32:
Closed: Internal fan OK (also with non-powered fan)
Open: Internal fan in over temperature alarm
Power the internal fan (max 1200W) with a three-phase voltage on terminals U3/V3/W3.
Type of fan compliant 2009/125/CE (ErP)
ADV200 starting from S/N 33GN071493
3 x 380...480V
(±10%) 50/60Hz,
1.9 ... 1.7 Arms
Ground
250V/10A contact
OK inverter fan contact management terminals 31-32:
Closed: Inverter fan OK and powered;
Open: Inverter fan in alarm or not supplied.
Power the internal fan (max 1200W) with a three-phase voltage on terminals U3/V3/W3.
(1) For each module.
(2) ADV200-73150-KXX-4A and ADV200-73551-KXX-4A models.