ADV200 • Quick start up guide 159
10.2 Choke
10.2.1 Optional input chokes (L1)
A three-phase mains choke is mandatory for sizes of ≥ 160 kW.
Use of mains chokes with an impedance of at least 3% is recommended.
The table below shows the minimum inductance values and current ratings with
the codes proposed by Gefran.
In case of a Master and Slave connection (400 kW to 1 MW devices) the use of
identical chokes (same inductance value and same current rating) for Master drive
and for each Slave drive is mandatory to ensure the correct distribution of current
over the drive input rectier bridges.
Sizes
Inverter
Output
Mains
inductance
(mH)
Rated
current
(A)
Saturation
current
(A)
Type Code
Dimensions
(WxHxd,
mm) and
Weights
1007 ... 61320 HD / LD Integrated on DC-link
71600
HD 0.085 309 618 LR3-160 S7D40
300 x 270 x
260, 44kg
LD 0.085 420 710 LR3-200 S7AE9
300 x 270 x
355, 54kg
72000 HD / LD 0.085 420 710 LR3-200 S7AE9
72500 HD / LD 0.06 550 1050 LR3-315 S7D28
375 x 400 x
220, 74kg
73150 HD / LD 0.04 700 900 LR3-ADV-355 S7LR01
390 x 400 x
290, 83kg
73551 HD / LD 0.04 700 900 LR3-ADV-355 S7LR01
400 kW
ADV-72000-KXX-4-MS 04
HD / LD
0.085 420 710 LR3-200 S7AE9
300 x 270 x
355, 54kg
ADV-72000-XXX-4-SL
0.085 420 710 LR3-200 S7AE9
500 kW
ADV-72500-KXX-4-MS 05
HD / LD
0.06 550 1050 LR3-315 S7D28
375 x 400 x
220, 74kg
ADV-72500-XXX-4-SL
0.06 550 1050 LR3-315 S7D28
630 kW
ADV-73150-KXX-4-MS 06
HD / LD
0.04 700 900 LR3-ADV-355 S7LR01
390 x 400 x
290, 83kg
ADV-73150-XXX-4-SL
0.04 700 900 LR3-ADV-355 S7LR01
710 kW
ADV-73551-KXX-4-MS 07
HD / LD
0.04 700 900 LR3-ADV-355 S7LR01
ADV-73551-XXX-4-SL
0.04 700 900 LR3-ADV-355 S7LR01
900 kW
ADV-73150-KXX-4-MS 09
HD / LD
0.04 700 900 LR3-ADV-355 S7LR01
ADV-73150-XXX-4-SL
0.04 700 900 LR3-ADV-355 S7LR01
ADV-73150-XXX-4-SL
0.04 700 900 LR3-ADV-355 S7LR01
1 MW
ADV-73551-KXX-4-MS 10
HD / LD
0.04 700 900 LR3-ADV-355 S7LR01
ADV-73551-XXX-4-SL
0.04 700 900 LR3-ADV-355 S7LR01
ADV-73551-XXX-4-SL
0.04 700 900 LR3-ADV-355 S7LR01
10.2.2 Optional external choke (L2)
On 400 kW to 1 MW devices, output chokes must be used: value and their techni-
cal characteristics MUST be the same for all the drive power modules (same
inductance value and same current rating) to garantee correct current sharing.
Cable lenght must be the same between the drive power modules.
Caution
Attention

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 Series and is the answer not in the manual?

gefran ADV200 Series Specifications

General IconGeneral
Brandgefran
ModelADV200 Series
CategoryController
LanguageEnglish

Related product manuals