60 ADV200 • Quick start up guide
• an optional USB/ RS232 adapter, code 8S8F62 (including the cable for USB
connection)
• shielded cable for the XS / PCI-COM (or PCI-485) connection, code 8S864C,
see gure 5.5.1.1 .
5.5.2 Drive / RS485 port point-to-point connection (with insulation)
To make the connection with galvanic isolation, the OPT-RS485-ADV optional
card is required.
The card is equipped with a 9-pin D-SUB male receptacle connector which must
be inserted in the XS connector of the ADV200 drive.
Connect terminals 1, 2 and 4 to the serial line as shown in the gure below; for
the connection from the serial line to the PC, the adapters indicated in paragraph
5.5.1 must be used.
XS
Terminal
1
2
3
4
Name
TxA /RxA
TxB /RxB
Reserved
EQP (Equipotentiality)
Switch
S1
Function
Closing of terminations
Figure 5.5.2.1: OPT-RS485-ADV card
5.5.3 RS 485 multi-drop connection
For the multi-drop connection, the OPT-RS485-ADV optional card must be in-
stalled on each drive; the ends of the connection must have S1 termination switch
set to ON (for point 3: ON only on the rst).
The multi-drop connection is always galvanically insulated.
Up to 20 drives can be connected; the maximum length of the connection is 200
meters.
1) Multidrop connection between ADV200 and an industrial PC with RS485
output
See gure 5.5.3.1. The connection requires:
• an optional OPT-RS485-ADV card for each ADV200,
• shielded wires to connect the OPT-RS485-ADV to the PC.
2) Multidrop connection between ADV200 and a PC with RS232 output
See gure 5.5.3.2. The connection requires:
• an optional OPT-RS485-ADV card for each ADV200,
• shielded wires to connect the OPT-RS485-ADV to the PC, and an optional
PCI-COM adapter (code S560T).
3) Multidrop connection between ADV200 and a PC with USB output
See gure 5.5.3.3. The connection requires:
• an optional OPT-RS485-ADV card for each ADV200,
• a USB-RS485 Serial converter interface (8S8F60).