40 ADV200 • Quick start up guide
5.1.11 Parallel DC connection
In the case of DC power supply, insertion of an AC mains inductance on the power
supply input of the power supply unit is compulsory (for the type of inductance,
consult the manual of the power supply unit).
To avoid to damage the integrated EMI lter, AFE200 regenerative power supply
unit may not supply the DC power supply to standard ADV1007 ...ADV61320
drives, version ADV....-IT must be used.
FFE200 Regenerative power supply unit may supply the DC power supply to
the standard ADV200, ADV200-...-DC and ADV....-IT series.
M1
3
M2
3
U
V
W
C
D
ADV200 (1)
U
V
W
C
D
ADV200 (2)
M..
3
U
V
W
C
D
ADV200 (..)
K1M
L1
L2
L3
F1 (*)
( 400 V / 460 50/60 Hz)
AC
3ph - V
AC
,
L1 (*)
F12
F22
F..2
M3
3
U
V
W
C
D
ADV200 (3)
F32
AFE200, FFE200,
SMB200, SM32 or
DC Power supply
(*) Refer to AFE200, FFE200, SMB200, SM32 or DC Power supply manual.
Note! For size 7 only, adaptation for internal mounting of “F12, F22, F32, F.2” fuses (DC side) on request