XNX Universal Transmitter
Warnings/Faults
135
Informational Messages
Number Description Contents of Data Field
I001 Unused
I002 Force Relay Mode Started Bitpattern for relays. (E.G. 7.0 ==All)
I003 Force Relay Mode Ended. N/A
I004 Force mA Mode Started Force current. (E.G. 20.0)
I005 Force mA Mode Ended N/A
I006 Short-Term Inhibit Started N/A
I007 Short-Term Inhibit Ended N/A
I008 Long-Term Inhibit Started N/A
I009 Long-Term Inhibit Ended N/A
I010 mA Output Recalibrated N/A
I011 Bump Test Started N/A
I012 Bump Test Timed Out N/A
I013 Bump Test Completed Concentration < Al1 Peak concentration observed
I014
Bump Test Completed
Al1 < Concentration < Al2
Peak concentration observed
I015 Bump Test Completed. Al2 < Concentration Peak concentration observed
I016 Zero Calibration Successful N/A
I017 Zero Calibration Failed Error code
I018 Calibrate Span Successful 1 of 2 Percent change in span factor from previous
I019 Calibrate Span Successful 2 of 2 Absolute span factor
I020 Calibrate Span Failed Error code
I021 Calibrate Span Timeout N/A
I022 Password Changed 1,2 or 3 (access level)
I023 Performing Soft Reset N/A
I024 Alarms Configured Latching N/A
I025 Alarms Configured Non-Latching N/A
I026
Alarm Relays Configured Normally
Energized
N/A
Number Description Contents of Data Field
I027
Alarm Relays Configured Normally De-
Energized.
N/A
I028 Fieldbus Address Changed New address (e.g. 15)
I029 Fieldbus Speed Changed New speed (e.g. 19200)
I030 Sensor Type Changed iCurrentCalGlobalID
I031 Gas Selection Changed iCurrentCalGlobalID
I032 Time For Beam Block Fault Changed iBlockFltTime
I033 Time For Fault Detection Changed iOtherFltTime
I034 Level For Low Signal Fault Changed fLowSignalLevel
I035 Invalid Path Length Written fPathLen
I036 Path Length Changed fPathLen
I037 mA for Inhibit Changed f_mA_Flt_Step[0]
I038 mA for Warning Changed f_mA_Flt_Step[1]
I039 mA for Overrange Changed f_mA_Flt_Step[2]
I040 mA for Fault Changed f_mA_Flt_Step[3]
I041 mA for Low Signal Changed f_mA_Flt_Step[4]
I042 mA for Blocked Beam Changed f_mA_Flt_Step[5]
I043 Concentration for mA Full Scale Changed fDisplayRange
I044 Instrument Id Changed N/A
I045 Measuring Units Changed iMeasurementUnits
I046
Alarm 1 Reconfigured for Increasing
Concentrations
N/A
I047
Alarm 1 Reconfigured for Depleting
Concentrations
N/A
I048
Alarm 2 Reconfigured for Increasing
Concentrations
N/A
I049
Alarm 2 Reconfigured for Depleting
Concentrations
N/A
I050 Alarm 1 Value Changed fAlarmThres[0]
I051 Alarm 2 Value Changed fAlarmThres[1]
I052
Clock Set N/A