XNX Universal Transmitter
Specications
157
Notes
Special notes for ISA 60079-29-1:2013 approval:
This approval covers XNX in combination with Searchpoint Optima Plus and MPD catalytic sensors only.
This approval allows direct tment of the Searchpoint Optima Plus or MPD catalytic sensors to the XNX with a load 250 ohm minimum resistance. This approval
does not cover the remote-mounting of the sensor from the XNX.
XNX shall be installed such that the MPD sensor faces downwards. When using the Searchpoint Optima Plus sensor this must be mounted so that the sensor is
horizontal.
For the ISA 60079-29-1 assessment, only the 4 to 20 mA output is considered as the safety function. None of the other outputs of the XNX are considered as the
safety function during this assessment.
For the compliance to this approval, the adjustable alarm set point shall not exceed 60 %LEL and the highest alarm shall be congured as a latching alarm.