XNX Universal Transmitter
Installation and Operation
86
Figure 137. Modbus Options screen
From the Set Fieldbus Address screen, select
✓
. To set the
Fieldbus address, use the
switches to move to the desired
position and use
✓
to select it. Use the switches to
decrease or increase the value until the desired value appears.
Use
✓
to select the value and moves to the next setting.
Figure 138. Set Fieldbus Address and Address Value screens
The communications baud rate can be set from this screen. Use
the switches to highlight the proper baud rate and select
✓
.
✓
Figure 139. Set Baud Rate screens
Once the values for the Fieldbus address have been set, use
the
switches to navigate to the ‘ü’ then select it to save the
changes.
Figure 140. Accept Settings and Fieldbus Address Settings Accepted screens
Configure Security
Congure Security is used to set or reset the level 1 and level 2
passcodes that control access to the conguration menus of the
transmitter.
Figure 141. Congure Security screens
Easy Reset from Main Status
The Easy Reset from Main Status option controls the ability
to reset faults, warnings, and alarms from the General Status
screen (see The General Status Screen).
Use the switches and
✓
to select the lock icon . The Lock/
Unlock screen will be displayed. Choose ‘Lock’
to prevent reset
without password access. The ‘Unlock’
choice allows resets
without requiring login or a passcode.
Figure 142. Lock/Unlock screen