XNX Universal Transmitter
Introduction
12
20 mA/HART Output
All XNX Transmitters provide a 20mA Current Loop with HART
Communication which can be user congured for Sink, Source
(3-Wire) or Isolated (4-Wire) electrical interface based on
installation requirements.
The 20mA current loop output provides an analog indication of
special states, a proportional output to gas concentration and
overrange indication as shown in the table below. In the event of
a simultaneous alarm and fault, an alarm condition will always
override fault or warning state.
Output Description* Notes
1.0 mA Fault
Special
State
Indication
2.0 mA
Warm-up
Inhibit
Bump Test
Calibration
3.0 mA Warning
4-20 mA Gas Concentration
21 mA Overrange
*Alarm conditions always take priority over faults and warnings.
HART Protocol provides communications with the transmitter
from a remote control system for Conguration, Status, and
Diagnostics. (See the HART Protocol section for additional
information)
Communications
The XNX
®
Universal Transmitter is registered with the HART
®
Communication Foundation. The transmitter
features HART over 4-20mA as standard.
Additional optional communication interfaces are available:
relay communication, Modbus, or FOUNDATION Fieldbus.
Each communication option has a dedicated option board. For
additional information, refer to the Options section.
Certifications
XNX-UT**-****** Versions are UL and CSA listed for installation in
Class I, Division 1, Groups A, B, C and D Hazardous Locations.
FM Approvals evaluation includes Class I, Zone 1, Group IIC,
as well as performance tests for specic sensor/transmitter
combinations. The CSA or FM certication does not cover daisy-
chained XNX combustible gas transmitters, the use of HART,
Modbus, or FOUNDATION Fieldbus protocols for combustible
gas performance. HART, Modbus, or FOUNDATION Fieldbus
protocols can be used only for data collection or record keeping
with regards to combustible gas. The EC cartridge
2
and EC
remote mount kit are UL classied to Canandian and US
standards.
XNX-AM **-***** versions are certied to comply with the
European Community ATEX Directive and the prescribed
protection methods for installation in potentially explosive
atmospheres.
XNX-BT**-***** versions are UL listed and INMETRO approved for
compliance with both U.S. and Brazilian standards.
See the Sensor Data section for additional information on
applicable approvals by part number and the Operating and
Storage Conditions for Performance Tested EC Sensors section
for marking.
2
“Cartridge” and “sensor” are used interchangeably in this document.

Table of Contents

Other manuals for Honeywell XNX-UT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX-UT Series and is the answer not in the manual?

Honeywell XNX-UT Series Specifications

General IconGeneral
BrandHoneywell
ModelXNX-UT Series
CategoryTransmitter
LanguageEnglish

Related product manuals