Source/Circuit
type
Source voltage
(nominal)
Plug or connector
type
Power receptacle
required
Number of power
cords required
(per enclosure
leaving the rack)
Single-phase 63 A 200–240 VAC
50/60 Hz
IEC 309 63 A
Single Phase Blue,
3.6 m (11.8 ft)
power cord
IEC 309 63 A
Single Phase, Blue
4
Single-phase 30 A 200–240 VAC
50/60 Hz
NEMA L6-30P
Single Phase,
3.6 m (11.8 ft)
power cord
NEMA L6-30R
Single Phase
6
More information
Generic Site Preparation Guide
Environmental specifications
Temperature and humidity specifications
The following table contains the allowed and recommended temperature and humidity limits for both
operating and nonoperating Integrity Superdome X systems.
Specification Value
Temperature range
1
Allowable Operating Range
2
+5° C to +40° C (41° F to 104° F)
Recommended Operating Range +18° C to +27° C (64° F to 81° F)
Nonoperating (powered off) +5° C to +45° C (41° F to 113° F)
Nonoperating (storage) -40° C to +80° C (-40° F to 176° F)
Humidity Range (noncondensing)
Allowable Operating Range -12° C DP and 8% RH to +24° C DP and 85% RH
Recommended Operating Range +5.5° C DP to +15° C DP and 65% RH
Nonoperating (powered off) 8% RH to 90% RH and 29° C DP
Nonoperating (storage) 8% RH to 90% RH and 32° C DP
1
All temperature ratings shown are for sea level. An altitude derating of 1° C per 300 m above 900 m is
applicable. No direct sunlight allowed. Upper operating limit is 3,048 m (10,000 ft) or 70 Kpa/10.1 psia.
Upper nonoperating (storage) limit is 9,144 m (30,000 ft) or 30.3 KPa/4.4 psia.
2
The Recommended Operating Range is recommended for continuous operation. Operating within the
Allowable Operating Range is supported but might result in a decrease in system performance.
28 Environmental specifications