GD200A series VFD Fault tracking
-124-
Ensure there is no weeping
and distortion to the capacitors.
Visual
examination or
estimate the
usage time
according to the
maintenance
information
Estimate whether there is
abnormal noise and vibration.
Hearing and
Visual
examination or
rotate with hand
Estimate there is no losses
screw.
Ensure there is no
color-changing caused by
overheating.
Visual
examination or
estimate the
usage time
according to the
maintenance
information
Ensure whether there is stuff or
foreign objection in the cooling
fan, air vent.
Consult the local service representative for more details on the maintenance. Visit the official
website of INVT http: //www.invt.com and choose Service.
8.8.2 Cooling fan
The VFD's cooling fan has a minimum life span of 25,000 operating hours. The actual life span
depends on the VFD usage and ambient temperature.
The operating hours can be found through P07.14 (accumulative hours of the VFD).
Fan failure can be predicted by the increasing noise from the fan bearings. If the VFD is operated in
a critical part of a process, fan replacement is recommended once these symptoms appear.
Replacement fans are available from INVT.
8.8.2.1 Replacing the cooling fan
Read and follow the instructions in chapter 1 Safety precautions. Ignoring the
instructions would cause physical injury or death, or damage to the equipment.