GD200A series VFD Function parameters
-73-
Bus voltage at the last but one fault
The max. temperature at the last but one fault
Input terminals state at the last but one fault
Output terminals state at the last but one fault
P08 Group Enhanced function
Refer to P00.11 and P00.12 for detailed definition.
Goodrive200A series define four groups of
ACC/DEC time which can be selected by P5
group. The first group of ACC/DEC time is the
factory default one.
Setting range: 0.0–3600.0s
This parameter is used to define the reference
frequency during jogging.
Setting range: 0.00Hz –P00.03 (the max.
frequency)
The jogging ACC time means the time needed if
the VFD runs from 0Hz to the max. frequency.
The jogging DEC time means the time needed if
the VFD goes from the max. frequency (P00.03) to
0Hz.
Setting range: 0.0–3600.0s
When the set frequency is in the range of jumping
frequency, the VFD will run at the edge of the
jumping frequency.
The VFD can avoid the mechanical resonance
point by setting the jumping frequency. The VFD
Jumping
frequency
range 1