GD200A series VFD Function parameters
-91-
1: Overload integral is valid
Setting range: 0000–1131
Detection level
of underload
pre-alarm
If the VFD current or the output current is lower
than P11.11, and its lasting time is beyond
P11.12, the VFD will output underload pre-alarm.
Setting range of P11.11: 0–P11.09
Setting range of P11.12: 0.1–3600.0s
Detection time
of underload
pre-alarm
Output terminal
action during
fault
Select the action of fault output terminals on
undervoltage and fault reset.
0x00–0x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
Extension
functions
selection
0x00–0x11
LED ones: Voltage drop frequency-decreasing
selection
0: Voltage drop frequency-decreasing selection
disable
1: Voltage drop frequency-decreasing selection
enable
LED tens: Step 2 ACC/DEC time option
0: Step 2 ACC/DEC time option disable
1: Step 2 ACC/DEC time option enable,when
running frequency more than P08.36, ACC/DEC
time switch to step 2 ACC/DEC time
P13 Group Enhanced function parameters
Braking current
of short-circuit
When P01.00=0 during the starting of the VFD, set
P13.14 to a non-zero value to enter the short
circuit braking.
When the running frequency is lower than P01.09
during the stopping of the VFD, set P13.15 to a
non-zero value to enter into stopping short
circuited braking and then carry out the DC
braking at the time set by P01.12 (refer to the
instruction of P01.09–P01.12).
Braking
retention time
before starting
Braking
retention time
when stopping