GD200A series VFD Function parameters
-90-
Function
code
Name
Description
Default
value
Modify
0: Valid
1: Invalid
Setting range of P11.06: 50.0200.0%
Setting range of P11.07: 0.0050.00Hz/s
P11.08
Overload
pre-alarm of
the motor/VFD
The output current of the VFD or the motor is
above P11.09 and the lasting time is beyond
P11.10, overload pre-alarm will be output.
Output current
Overload
pre-alarm
point
T
T
Y,
RO1, RO2
Pre-alarm
time
Pre-alarm
time
Setting range of P11.08:
Enable and define the overload pre-alarm of the
VFD or the motor.
LED ones:
0: Overload pre-alarm of the motor, comply with
the rated current of the motor
1: Overload pre-alarm of the VFD, comply with the
rated current of the VFD
LED tens:
0: The VFD continues to work after underload
pre-alarm
1: The VFD continues to work after underload
pre-alarm and the VFD stops running after
overload fault
2: The VFD continues to work after overload
pre-alarm and the VFD stops running after
underload fault
3. The VFD stops when overload or underload.
LED hundreds :
0: Detection all the time
1: Detection in constant running
LED thousands: Overload integral selection
0: Overload integral is invalid
0x000
P11.09
Overload
pre-alarm test
level
G type:
150%
P type:
120%
P11.10
Overload
pre-alarm
detection time
0x0000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive200A Series and is the answer not in the manual?

INVT Goodrive200A Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive200A Series
CategoryDC Drives
LanguageEnglish

Related product manuals