GD200A series VFD Function parameters
-88-
0: Seconds; the running time of all steps is
counted by second
1: Minutes; the running time of all steps is counted
by minute
P11 Group Protective parameters
0x00–0x11
LED ones:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED tens:
0: Output phase loss protection disable
1: Output phase loss protection enable
LED hundreds:
0: Input phase loss hardware protection disable
1: Input phase loss hardware protection enable
Sudden power
loss frequency
decrease
Frequency
decrease ratio
of sudden
power loss
Setting range: 0.00Hz/s–P00.03 (max. frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency-decreasing point,
the VFD begin to decrease the running frequency
at P11.02, to make the VFD generate power
again. The returning power can maintain the bus
voltage to ensure a rated running of the VFD until
power recovery.
Frequency decrease point
at sudden power loss
Note:
1. Adjust the parameter properly to avoid the
stopping caused by VFD protection during the
switching of the grid.
2. Disable input phase loss protection to enable
this function.