GD200A series VFD Fault tracking
-116-
Keypad
communication
fault
The connection of the
keypad wires is not good or
broken
The keypad wire is too long
and affected by strong
interference
There is circuit fault on the
communication of the keypad
and main board
Check the keypad wires
and ensure whether there is
mistake
Check the environment and
avoid the interference source
Change the hardware and
ask for service
Parameters
downloading fault
The connection of the
keypad wires is not good or
broken
The keypad wire is too long
and affected by strong
interference
There is mistake on the
data storage of the keypad
Check the keypad wires
and ensure whether there is
mistake
Change the hardware and
ask for service
Repack-up the data in the
keypad
Electronic
underload fault
The VFD will report the
underload pre-alarm
according to the set value
Check the load and the
underload pre-alarm point