GD200A series VFD Communication protocol
-137-
ASCII master command message (the
command sent by the master to the VFD)
ASCII slave response message (the message
sent by the VFD to the master)
High bit of write data
address
High bit of write data
address
Low bit of write data
address
Low bit of write data
address
9.4.2.4 Command code: 10H, continuous writing function
Command code 10H means the master write data to the VFD, the number of data being written is
determined by the command "data number", the max. number of continuous writing is 16 words.
For instance: Write 5000 (1388H) to 0004H of the VFD whose slave address is 02H, write 50 (0032H)
to 0005H of the VFD whose slave address is 02H, then the structure of this frame is listed as below:
ASCII master command message (the
command sent by the master to the VFD)
ASCII slave response message (the message
sent by the VFD to the master)
High bit of starting
address
High bit of starting
address
Low bit of starting
address
Low bit of starting
address