Commissioning
Setting the IP configuration of the Inverter Drive 8400 motec
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Setting the IP configuration of the Inverter Drive 8400 motec
The IP configuration is required for addressing the Inverter Drive 8400 motec in order to establish
communication between the PC/»Engineer« or the scanner and the inverter via EtherNet/IP. This
requires allocation of an IP address, subnet mask, and gateway address. You can allocate these IP
parameters for the Inverter Drive 8400 motec by means of the following options:
• Setting via the EtherNet/IP configurator of the »Engineer«
( 32)
• Setting via codes in the »Engineer«
( 34)
• Setting via a BOOTP/DHCP server
( 36)
• Setting via the TCP/IP Interface Object (0xF5)
( 36)
Note!
• The assignment of invalid combinations of IP address, subnet mask, and gateway
address can have the consequence that no connection to the EtherNet/IP network can
be established.
•Codes C13010
(IP address), C13011 (subnet mask), C13012 (gateway address), and
C13016
(multicast IP address) show the IP parameters currently used.
• In the case of impermissible settings, the error message EtherNet/IP: Invalid IP
Parameters [0x01bc6533] ( 85) is output.