(12) Inspection report
1) Project information
 Checker Date

Heat pump water heater Hot water storage cylinder

Model name  Model name 
Check items Standard
Checked result

Installation work

installed on the level?
Check with level gauge

with anchor bolt?
Check technical manual


heat pump water heater and the HW storage unit?
Check strength and level

Is the drainage from the heat pump water heater and the HW
storage unit OK?
Check technical manual


the HW storage unit secured?
Check technical manual





installed in circumstance surrounded by oil and special gases


 
Is the limitation for installation and piping preserved? Check technical manual

Is the drain valve closed? Is the feed water valve open? Check open or close
Water piping work

resistance and thermal resistance?
Check technical manual


piping
Check technical manual

Is the insulation work done properly? Check technical manual

Is the cleanable strainer attached to the inlet port of feed water? 60 mesh or more
 
Can water be drained or stopped normally by operating drain
valve and relief valve?
E nable to drain and stop
water normally
Can air purge be done? Check operability of air
purge valve
Can water be drained from drain piping well? 
Can water be drained from drain ditch well? Drainage performance of
drain ditch


Check measures
E lectric work

thickness comform with the standard?
Check technical manual

 Check tightening
Is grounding work done surely? Check technical manual



Check clamp and outlook
of wire
Is the insulation resistance enough? Is the imbalance between
phases within the standard?
Imbalance between



Do not run parallelly
Others

surface?
Check no anomaly on the
unit surface


Check operation
Is the hot water supply volume OK? Check hot water supply
2) Check list for installation
: OK
: shall be revised
: No item
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries ESA30E-25 and is the answer not in the manual?

Mitsubishi Heavy Industries ESA30E-25 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelESA30E-25
CategoryHeat Pump
LanguageEnglish

Related product manuals