NISSEI CORPORATION E6581815
F-17
6
Starting frequency 
Output frequency (Hz)
0
Operation signal (F-CC)
Time
ON
OFF
6.5 Operation frequency
6.5.1 Starting frequency
 : Starting frequency
Function
The frequency set with  is put out as soon as operation is started.
[Parameter setting]
Title Function Adjustment range Default setting
 Starting frequency 0.1-10.0 (Hz) 0.1
6.5.2 Run/stop control with frequency setting signals
 : Operation starting frequency
 : Operation starting frequency hysteresis
Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title Function Adjustment range Default setting
 Operation starting frequency 0.0- (Hz) 0.0

Operation starting frequency hysteresis 0.0- (Hz) 0.0
0 A B 100% Frequency command value
 + 
 - 

When the frequency command signal
reaches the B point, the inver t er
operates.
When decelerating, operation stops
when the frequency setting signal is less
than point A.
Output frequency [Hz]
