NISSEI CORPORATION E6581815
F-1
6
6. Other parameters
Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. Modify
parameter settings as required. Refer to section 11 tables of extended parameters.
6.1 Input/output parameters
6.1.1 Low-speed signal
 : Low-speed signal output frequency
Function
When the output frequency exceeds the setting of  an ON signal will be generated.
This signal can also be used as an operation signal when  is set to 0.0Hz, because an ON
signal is put out if the output frequency exceeds 0.0Hz.
+ Output from the open collector output terminal OUT.
Output from relay output FLA-FLB-FLC is possible depending on the parameter settings.
[Parameter setting]
Title Function Adjustment range Default setting
 Low-speed signal output frequency 0.0 -  (Hz) 0.0
Output frequency
Time [s]

Low-speed detection signal :
OUT-NO terminals
ON
OFF
Inversion of low-speed
detection signal
ON
OFF
[Hz]
0
Setting frequency
, When FM terminal is used as the open collector terminal, it needs to switch to the slide switch SW3 (OUT2).