Specifications of the Relay Output Terminals
•The relay output terminals are set to the SPDT contact. The following shows their operations.
Electrical specifications
Output terminal Resistance load Inductive load
MA-MC
Max. contact
capacity
250 V AC, 2 A
30 V DC, 3 A
250 V AC, 0.2 A
30 V DC, 0.6 A
Min. contact
capacity
100 V AC, 10 mA
5 V DC, 100 mA
MB-MC
Max. contact
capacity
250 V AC, 1 A
30 V DC, 1 A
250 V AC, 0.2 A
30 V DC, 0.2 A
Min. contact
capacity
100 V AC, 10 mA
5 V DC, 100 mA
Inside the Inverter
(Factory default)
MB
MA
MC
(a) When used as an alarm terminal (b) When used as an output terminal
C036
set
value
Power
supply
Inverter
status
Output terminal status C036
set
value
Power
supply
Output
signal
Output terminal status
MA-MC MB-MC MA-MC MB-MC
00
ON
Fault Closed Open
00
ON
ON Closed Open
Normal Open Closed OFF Open Closed
OFF ⎯ Open Closed OFF ⎯ Open Closed
01
ON
Fault Open Closed
01
ON
ON Open Closed
Normal Closed Open OFF Closed Open
OFF ⎯ Open Closed OFF ⎯ Open Closed

Table of Contents

Other manuals for Omron 3G3JX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3JX and is the answer not in the manual?

Omron 3G3JX Specifications

General IconGeneral
BrandOmron
Model3G3JX
CategoryInverter
LanguageEnglish

Related product manuals