2-24
2-2 Wiring
2
Design
*3. Below are the contact specifications of the relay output.
*4.
By factory default, the relay output (MA, MB) contact selection (C036) is set at NC contact between MA-MC, and
NO contact between MB-MC.
Mode Selector
RS-485 Communication/Operator Selector (S7)
Select the mode according to the option connected to the communications connector.
When using the 3G3AX-OP01 supplied with the Inverter, it is available regardless of the switch
condition.
Emergency shutoff selector (S8)
Use this selector to enable the emergency shutoff input function.
*1 The multi-function input terminal 3 is switched to a terminal for emergency shutoff input, and the allocation of
other multi-function input terminals is also changed automatically. Do not set to ON immoderately. For details,
refer to "Emergency Shutoff Input Function" (page 4-45).
Output
terminal
Contact
capacity
Resistance load Inductive load
MA-MC
Max.
250 V AC 2.5 A
30V DC 3 A
250 V AC 0.2 A
30 V DC 0.7 A
Min.
100 V AC 10 mA
5 V DC 100 mA
MB-MC
Max.
250 V AC 1 A
30 V DC 1 A
250 V AC 0.2 A
30 V DC 0.2 A
Min.
100 V AC 10 mA
5 V DC 100 mA
Symbol Name Status Description
S7
RS-485 communication/
operator selector
485 RS485 ModBus communication
OPE [Default] Digital Operator (Option: 3G3AX-OP1)
Symbol Name Status Description
S8
Emergency
shutoff
selector
ON Emergency shutoff input enabled
*1
OFF
[Default]
Normal

Table of Contents

Other manuals for Omron 3G3JX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3JX and is the answer not in the manual?

Omron 3G3JX Specifications

General IconGeneral
BrandOmron
Model3G3JX
CategoryInverter
LanguageEnglish

Related product manuals