4-2 Function Mode
4
Functions
Control Method (V/f Characteristics)
You can set V/f characteristics (output voltage/output frequency).
* To switch to the 2nd/3rd control, allocate 08 (SET)/17 (SET3) to the desired multi-function input and then turn it
on.
*1. Refer to "Sensorless Vector Control" (page 4-116).
*2. Refer to "0-Hz Sensorless Vector Control" (page 4-117).
ï‚¢Constant Torque Characteristics (VC)
Output voltage is proportional to output frequency.
While proportional from 0 Hz to base frequency, the output voltage is constant from base to
maximum frequencies.
Parameter No. Function name Data Default setting Unit
A044
V/f characteristics
selection
Heavy duty
00: VC (Constant torque characteristics)
01: VP (Special reduced torque
characteristics)
02: Free V/f (characteristics)
(Only A044/A244 can be set.)
03: SLV (Sensorless vector control)
(Only A044/A244 can be set.
*1
)
04: 0SLV (0-Hz sensorless vector
control)
(Only A044/A244 can be set.
*2
)
05: V2 (Sensor vector control)
(Only A044/A244 can be set.)
Normal duty
00: VC (Constant torque characteristics)
01: VP (Special reduced torque
characteristics)
02: Free V/f (characteristics)
03: SLV (Sensorless vector control)
00 
A244
*2nd V/f characteristics
selection
A344
*3rd V/f characteristics
selection
Related functions A046, A246, A047, A247, A082, H003, H203, H004, H204
0
Output voltage
(100%)
Base frequency
Output
frequency (Hz)
Max. frequency