4-48
4-2 Function Mode
4
Functions
Free Setting
To protect the motor according to load, you can freely set the electronic thermal characteristics.
Below is the setting range.
ï‚¢Thermal Warning
•This function outputs an alarm signal before electronic thermal overheat protection is activated.
The warning level can be set in C061.
•Allocate 13 (THM) to any of multi-function output terminals 11 to 15 (C021 to C025) or the relay
output terminal (C026).
Tor que
x1.0
x0.8
0
540
Inverter output
frequency (Hz)
Output current
value (A)
b020
b018
b016
0
b015 b017 b019 A004/A204/A304
Max. frequency (Hz)
(Example) Output frequency = b017
(x): (b018/Rated current) × 109%
(y): (b018/Rated current) × 150%
(z): (b018/Rated current) × 200%
Trip time (s)
60
3.0
0 (x) (y) (z)
Motor current (A)
(Ratio to the rated
current of the Inverter)