4-110
4-2 Function Mode
4
Functions
ï‚¢FM Adjustment
•Adjust the Inverter output gain according to the meter connected to the FM terminal.
Analog Output AM/AMI Terminals
You can monitor the output frequency and current using the AM and AMI terminals on the control
circuit terminal block.
The AM terminal provides 0- to 10-V analog output.
The AMI terminal provides 4- to 20-mA analog output.
ï‚¢AM/AMI Selection
•Select a signal to output from the following table.
*1. This output is enabled only when "SLV", "0-Hz SLV", or "V2" is selected. (Refer to "Control Method (V/f
Characteristics)" (page 4-21).)
*2. Below are the specifications of the output torque (signed).
*3. In any other method the real output frequency of the inverter including compensations (different than d001
value) is displayed.
Parameter No. Function name Data Default setting Unit
C105 FM gain setting 50 to 200: Set a gain for the FM monitor. 100 %
Related functions C027, b081
Parameter
No.
Function name Data
Default
setting
Unit
C028/C029
AM selection
/
AMI selection
00: Output frequency (0 to Max. frequency (Hz)
*3
)
00 
01: Output current (0% to 200%)
02: Output torque
*1
(0% to 200%)
04: Output voltage (0% to 100%)
05: Power (0% to 200%)
06: Thermal load rate (0% to 100%)
07: LAD frequency (0 to Max. frequency [Hz])
09: Motor temperature (0ï‚°C to 200ï‚°C) (0ï‚°C output at 0ï‚°C or
lower)
10: Fin temperature
(0ï‚°C to 200ï‚°C) (0ï‚°C output at 0ï‚°C or lower)
11: Output torque (signed)
(AM output only. 0% to 200%
*1 *2
)
13: Drive programming output (YA1) (AM selection only)
14: Drive programming output (YA2) (AMI selection only)
19: Option board 1 (OP1) (AM selection only)
20: Option board 2 (OP2) (AM selection only)
AM output (V)
10
5
0
100 200
AM gain setting (C106) = 100%
AM gain setting (C106) = 200%
AM bias setting (C109) = 50%
Torque (%)

Table of Contents

Other manuals for Omron 3G3RX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3RX and is the answer not in the manual?

Omron 3G3RX Specifications

General IconGeneral
BrandOmron
Model3G3RX
CategoryDC Drives
LanguageEnglish

Related product manuals