4-97
4-2 Function Mode
4
Functions
ï‚¢Specifications of Multi-function Output Terminals 11 to 15
•Below are the specifications of multi-function output terminals 11 to 15.
ï‚¢Specifications of the Relay Output Terminals
•The relay output terminals have an SPDT contact configuration. Below is its operation.
(Example) When the relay output terminals are used for alarm
C031 to C035 set values
Power
supply
Output
status
Electrical characteristics
00
(NO contact)
ON
ON
Between each terminal and CM2
Voltage drop 4 V max. at power-on
Max. allowable voltage: 27 V DC
Max. allowable current: 50 mA
OFF
OFF 
01
(NC contact)
ON
ON
OFF
OFF 
Inside the Inverter
15
CM2
11
Inside the Inverter
AL0 AL2 AL1
(Default value: C036 = 01)
C036
set
values
Power
Inverter
status
Output terminal
status
Resistance load
Inductive load
AL2-
AL0
AL1-
AL0
AL2-
AL0
Max.
contact
capacity
250 V AC, 2 A
30 V DC, 8 A
250 V AC, 0.2 A
30 V DC, 0.6 A
00
ON
Abnormal Closed Open
Min.
contact
capacity
100 V AC, 10 mA
5 V DC, 100 mA
Normal Open Closed
AL1-
AL0
Max.
contact
capacity
250 V AC, 1 A
30 V DC, 1 A
250 V AC, 0.2 A
30 V DC, 0.2 A
OFF  Open Closed
Min.
contact
capacity
100 V AC, 10 mA
5 V DC, 100 mA
01
(Default)
ON
Abnormal Open Closed
Normal Closed Open
OFF  Open Closed