2-22
2-2 Wiring
2
Design
Wiring the Digital Operator
• The RX Series Inverter can be operated with the optional 3G3AX-OP01 or 3G3AX-OP05 as well
as the standard Digital Operator.
• To use the Digital Operator apart from the Inverter body, place an order for the optional cable
3G3AX-CAJOP300-EE (3 m).
• The optional cable should be 3 m or less. Using a cable longer than 3 m may cause malfunction.
Conforming to EC Directives
ï‚¢Conforming Standards
•EMC directive EN 61800-3: 2004
•Low-voltage directive EN 61800-5-1: 2007
ï‚¢Concept of Conformity
EMC Directive
OMRON products are the electrical devices incorporated and used in various machines or
manufacturing equipment. For this reason, we make efforts to conform our products to their related
EMC standards so that the machines or equipment which have incorporated our products should
easily conform to the EMC standards. The RX models have conformed to the EMC directive EN
61800-3 by following the installation and wiring method as shown below. Your machines or
equipment, however, vary in type, and in addition, EMC performance depends on the configuration,
wiring, or location of the devices or control panels which incorporate the EC directive conforming
products. This in turn does not allow us to confirm the condition and the conformity in which our
products are used. Therefore, we appreciate confirmation of the final EMC conformity for the whole
machine or equipment on your own.
Wiring the Power Supply
•Keep the ground cable as short as possible.
•Keep the cable between the Inverter and the noise filter as short as possible.
Connecting a Motor to the Inverter
•When connecting a motor to the Inverter, be sure to use shield braided cables.
•Keep the cables as short as possible.
Low-voltage Directive
The RX models have conformed to the EMC directive EN61800-5-1 by performing the machine in-
stallation and wiring as shown below.
•The RX models are an open type device. Be sure to install it inside the control panel.
•The power supply and voltage (SELV) with reinforced or double insulation should be used for
wiring to the control circuit terminals.
•To satisfy requirements of the LVD (low-voltage) directive, the Inverter must be protected with a
molded case circuit breaker (MCCB) in case a short-circuiting accident occurs. Be sure to install a
molded case circuit breaker (MCCB) on the power supply side of the Inverter.
•Use one molded case circuit breaker (MCCB) per Inverter.
•Use the crimp-type terminal with an insulation sleeve to connect to the main circuit terminals.

Table of Contents

Other manuals for Omron 3G3RX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3RX and is the answer not in the manual?

Omron 3G3RX Specifications

General IconGeneral
BrandOmron
Model3G3RX
CategoryDC Drives
LanguageEnglish

Related product manuals