5-1
5-1 Protective Functions and Troubleshooting
5
Maintenance Operations
5Maintenance Operations
5-1 Protective Functions and
Troubleshooting
Error Code List
Name Description Error Code Points to check and remedy
Reference
page
Overcurrent
trip
If the motor is
restrained or rapidly
accelerated or
decelerated, a large
current flows through
the Inverter, which
results in a
malfunction. The
current exceeding
the specified level
shuts off the output
and an error
appears.
This protection
function detects an
overcurrent through
the AC CT (current
detector).
The protection circuit
is activated at
approximately 220%
of the Inverter rated
output current and a
trip occurs.
Constant
speed
E01.0
Is there any rapid load fluctuation?
(Eliminate load fluctuation.)
Is there any output short-circuit?
(Check the output wires.)
Is there any ground fault?
(Check the output wires and motor.)

Deceleration E02.0
Is there any rapid deceleration?
(Increase the deceleration time.)
4-8
4-37
Acceleration E03.0
Is there any rapid acceleration?
(Increase the acceleration time.)
Has the motor shaft been locked?
(Check the motor and wires.)
Is the torque boost too high?
(Lower the torque boost.)
4-8
4-37
Others E04.0
Is the DC injection braking too high?
(Lower the injection breaking.)
Is there any error on CT?
(Replace or repair the CT.)
4-24
Overload
trip
*1
Monitors the Inverter output current
and shuts off the output, displaying
an error if the built-in electronic
thermal function detects overload
against the motor.
Trips depending on the electronic
thermal function settings.
E05.0
Is the load too large?
(Reduce the loading factor.)
Is the thermal level correct?
(Adjust the thermal level to an appropriate
level.)
Note: The electronic thermal function is set to
work easily at 5 Hz or lower. If a large
load inertial moment is applied, the
overload protect function works when
the motor starts accelerating, and the
load prevents it from accelerating. In
this case, increase the torque boost or
take other measures for adjustment.
4-46
Braking
resistor
overload
trip
Shuts off the output and displays an
error if the usage rate of
regenerative braking circuit exceeds
the b090 set value.
E06.0
Is there any rapid deceleration?
(Increase the deceleration time.)
Is the operation cycle frequent?
(Decrease the number of operation cycles.)
Is the usage rate setting of the regenerative
braking function low?
(Set to an appropriate level.)
Note: Pay attention to the allowable power of
the resistor.
4-8
4-74