4-24
4-2 Function Mode
4
Functions
Output Voltage Gain
•Changes the Inverter output voltage, based on the voltage selected in AVR voltage selection A082
as 100%.
•You can avoid motor hunting by reducing the output voltage gain.
DC Injection Braking
•DC injection braking is applied to the motor depending on the motor load.
•Two methods are available for DC injection braking: One is the external method via the multi-
function input terminal; the other is the internal method performed automatically to start/stop the
motor.
Even if DC injection braking is used, however, the motor may not stop depending on the moment
of inertia of the motor load.
Parameter No. Function name Data Default setting Unit
A045 Output voltage gain 20 to 100 100 %
Related functions A082
A045
AVR voltage
selection
(A082)
Base frequency
(A003/A203/A303)
Max. frequency
(A004/A204/A304)
Parameter No. Function name Data Default setting Unit
A051
DC injection braking
selection
00: OFF (Disabled)
01: ON (Enabled)
02: ON (FQ) (Frequency control [A052
set value])
00 
A052
DC injection braking
frequency
0.00 to 400.00 0.50 Hz
A053
DC injection braking
delay time
0.0 to 5.0 0.0 s
A054 DC injection braking power
0 to 100 (0.4 to 55 kW) 50
%
0 to 80 (75 to 132 kW) 40
A055 DC injection braking time 0.0 to 60.0 0.5 s
A056
DC injection braking
method selection
00: Edge operation
01: Level operation
01 
A057
Startup DC injection
braking power
0 to 100 (0.4 to 55 kW) 0
%
0 to 80 (75 to 132 kW) 0
A058
Startup DC injection
braking time
0.0 to 60.0 0.0 s
A059
DC injection braking
carrier frequency
0.5 to 15.0 (0.4 to 55 kW) 5.0
Hz
0.5 to 10.0 (75 to 132 kW) 3.0
Related functions C001 to C008