34
Maintenance Functions of DST1-series Safety I/O Terminals Section 1-7
1-7-4 Monitoring the Contact Operation Counters
Description
A DST1-series Safety I/O Terminal totals the number of times each safety
input contact, test output contact, and safety output contact turns ON and
internally saves the data in non-volatile memory. If the value of a counter
reaches the threshold value, the Connected Component Maintenance Flag in
General Status will turn ON.
Measurement count: 0 to 4,294,967,295 counts
(stored data: 0000 0000 to FFFF FFFF hex)
Measurement unit: Operations
Maximum resolution: 166.7 Hz
The user can monitor this information using the Network Configurator and
explicit messages.
Note One contact cannot be used at the same time for both the time and
count monitoring functions. Select only one of these in the Mainte-
nance Counter Mode Choice.
• If the Maintenance Counter Mode Choice is changed, the counter or
time data saved internally will be cleared.
This function does not operate when the I/O power supply is OFF.
Safety I/O Terminal
Record in the Slave
Number of times output
contact changes to ON.
Output device
(e.g., relay)
I/O power
Number of
operations