Rockwell Automation Publication 750-AT006D-EN-P - January 2022 65
Chapter 4 Auto Tuning
Figure 61 - Motor Parameter C/U Selector
These parameters only apply when 0:65 [Pri MtrCtrl Mode] = Induction SV (1), Induct Econ (2), Induction FV (3), IPM FV (4), or SPM FV (5).
Current Regulator Gain Calculation
Closed loop current regulator gains are calculated as functions of bandwidth and damping:
VCL CReg IdKp = Ld*2*B
W
VCL CReg IqKp = Lq*2*B
W
VCL CReg IdKi = VCL CReg IqKi = 2*B
W
*Rs/Damping
For IM motors:
B
W
= 10:445 [VCL CReg BW]
Damping = 10:450 [VCL CReg Damping]
Rs = 10:511 [c IM Stator Res] or 10:512 [u IM Stator Res]
Ld = Lq = 10:514 [c IM Leakage L] or 10:515 [u IM Leakage L]
For IPM and SPM motors:
B
W
= 10:445 [VCL CReg BW]
Damping = 10:450 [VCL CReg Damping]
Rs = 10:619 [c PM Stator Res] or 10:620 [u PM Stator Res]
Ld and Lq are the active values calculated by interpolation of autotune Ld and Lq values based on motor current.
Open loop current regulator gains for IPM and SPM motors are calculated as functions of bandwidth and damping:
VCL CReg IdKp = 2*B
W
*Ld100
VCL CReg IqKp = 2*B
W
*Lq75
VCL CReg IdKi = VCL CReg IqKi = 2*B
W
*Rs/Damping
MtrParam C/U Sel
Calculated
Calculated
User
Entered
510510
Automatic
Calculations
Motor Control
[Autotune] =
Static MtrID (IM only)
Or Rotate MtrID
Motor NP Amps
400
Motor NP Volts
401
Motor NP Hertz
402
Motor NP RPM
403
405
406
407
910
Motor NP Pwr Units
Motor NP Power
Motor Poles
Autotune
Motor NP Amps
400
Motor NP Volts
401
Motor NP Hertz
402
Motor NP RPM
403
405
406
407
910
Motor NP Pwr Units
Motor NP Power
Motor Poles
Autotune
000
= Read Only
000
= User Entered
000
= Read Only
000
= User Entered
620
627
629
637
639
614
643
645
647
649
651
641
512
515
518
521
524
490
u IM Stator Res (ohms)
u IM LeakageL (mH)
u Flux Cur Ref
u Slip RPM at FLA
u EncLs AngCmp
u IM StatResComp
Applies to IM Motors
Applies to PM Motors
620
627
629
637
639
614
643
645
647
649
651
641
512
515
518
521
524
490
u IM Stator Res (ohms)
u IM LeakageL (mH)
u Flux Cur Ref
u Slip RPM at FLA
u EncLs AngCmp
u IM StatResComp
Applies to IM Motors
Applies to PM Motors
642
644
646
648
650
640
619
626
628
636
638
613
511
514
517
520
523
489
c IM Stator Res (ohms)
c IM LeakageL (mH)
c Flux Cur Ref
c Slip RPM at FLA
c En cL s AngCm p
c IM StatResComp
Applies to IM Motors
Applies to PM Motors
642
644
646
648
650
640
619
626
628
636
638
613
511
514
517
520
523
489
c IM Stator Res (ohms)
c IM LeakageL (mH)
c Flux Cur Ref
c Slip RPM at FLA
c En cL s AngCm p
c IM StatResComp
Applies to IM Motors
Applies to PM Motors

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 755T Flux Vector Tuning and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 755T Flux Vector Tuning Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 755T Flux Vector Tuning
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals