3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions
130 6SE6400-5AW00-0BP0
3.5.7.20 Diagnostic parameters
r0035
CO: Motor temperature
Displays the measured motor temperature in °C.
r0036
CO: Frequency inverter utilization
Displays the frequency inverter utilization as a % referred to the overload. In so doing, the
value is calculated using the I
2
t model.
The I
2
t actual value relative to the maximum possible I
2
t value provides the level of
utilization.
r0052
CO/BO: Act. status word 1
Displays the first active status word (ZSW) of the frequency inverter (bit format) and can be
used to diagnose the inverter status.
r0054
CO/BO: Control word 1
Displays the first control word (STW) of the frequency inverter and can be used to display
the active commands.
r0063
CO: Actual frequency
Displays the actual frequency in Hz.
V/f
0
1,2
SLVC
(observer
model)
Encoder
P0400
P1300
160 ms
Frequency actual values:
Smoothed freq. actual value
Frequency actual value
Freq.act.value fr. the encoder
21,23
20,22
<20
0
P1300 = 21,23 and P0400 = 0 --> F0090
P0408 60
r0313
Smoothed speed act. value
r0313
60
r0022
r0021
r0063
r0061
r1079
CO: Selected frequency setpoint
Displays the selected frequency setpoint.
The following frequency setpoints are displayed:
r1078 total setpoint (HSW + ZUSW)
P1058 JOG frequency, clockwise
P1059 JOG frequency, counter-clockwise.
r1114
CO: Freq. setpoint after dir. ctrl.
Displays the setpoint (reference) frequency in Hz after the function block to reverse the
direction of rotation.
r1170
CO: : Frequency setpoint after RFG
Displays the total frequency setpoint (reference value) in Hz after the ramp-function
generator.

Table of Contents

Other manuals for Siemens MICROMASTER 440

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MICROMASTER 440 and is the answer not in the manual?

Siemens MICROMASTER 440 Specifications

General IconGeneral
Power Range0.12 kW to 250 kW
Output Voltage0 V to Input Voltage
Output Frequency0 Hz to 650 Hz
Control ModesVector control
Overload Capability150% for 60 seconds
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesPROFIBUS, DeviceNet, CANopen, Modbus RTU
Enclosure RatingIP20
Ambient Temperature-10°C to +50°C
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)