EasyManuals Logo

Siemens MICROMASTER 440 User Manual

Siemens MICROMASTER 440
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #254 background imageLoading...
Page #254 background image
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions
254 6SE6400-5AW00-0BP0
The sum of both torque setpoints is limited in the same way as the torque setpoint
of the speed control (refer to Section 3.23.2.5). Above the maximum speed (plus 3
%), a speed limiting controller reduces the torque limits in order to prevent the drive
accelerating any further.
A "real" closed-loop torque control (with automatically set speed) is only possible in
the closed-loop controlled range but not in the open-loop controlled range. In the
open-loop controlled range, the torque setpoint changes the setpoint speed
through a ramp-up integrator (integration time ~ P1499
*
P0341
*
P0342). This is
the reason that sensorless closed-loop torque control in the area around standstill
(0 speed) is only suitable for applications which require an accelerating torque
there and not a load torque (e.g. traversing drives). For closed-loop torque control
with sensors, this restriction does not apply.
If the closed-loop torque control is active, and a fast stop command (OFF3) is
output, then the system automatically changes-over to closed-loop speed control
and the drive is braked. If a normal stop command (OFF1) is output, there is no
changeover. Instead, the system waits until a higher-level control has brought the
drive to a standstill, in order to inhibit the pulses there. This is necessary in order to
allow the master and slave drives to be shut down together. For P1300 = 22 or 23,
for OFF1, the drive is directly powered-down (as for OFF2).
3.23.2.5 Limiting the torque setpoint
Parameter range: P1520 – P1531
P0640, r0067
r1407 bit 08, r1407 bit 09
Warnings -
Faults -
Function chart number: FP7700, FP7710
All of the following limits act on the torque setpoint which is either entered at the
speed controller output for closed-loop speed control or as torque input for closed-
loop torque control. The minimum is used from the various limits. This minimum is
cyclically computed in the drive inverter and displayed in parameters r1538, r1539.
¾ r1538 Upper torque limit
¾ r1539 Lower torque limit
This means that these cyclic values limit the torque setpoint at the speed controller
output / torque input and indicate the instantaneously maximum possible torque. If
the torque setpoint is limited in the drive inverter, then this is displayed using the
following diagnostic parameters
¾ r1407 bit 08 Upper torque limit active
¾ r1407 bit 09 Lower torque limit active

Table of Contents

Other manuals for Siemens MICROMASTER 440

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MICROMASTER 440 and is the answer not in the manual?

Siemens MICROMASTER 440 Specifications

General IconGeneral
Power Range0.12 kW to 250 kW
Output Voltage0 V to Input Voltage
Output Frequency0 Hz to 650 Hz
Control ModesVector control
Overload Capability150% for 60 seconds
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesPROFIBUS, DeviceNet, CANopen, Modbus RTU
Enclosure RatingIP20
Ambient Temperature-10°C to +50°C
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)

Related product manuals