Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions
6SE6400-5AW00-0BP0
57
3.1.2 Interconnecting signals (BICO technology)
A state-of-the-art drive unit must be able to interconnect internal and external
signals (setpoint / actual values and control / status signal). This interconnection
functionality must have a high degree of flexibility in order to be able to adapt the
drive to new applications. Further, a high degree of usability is required, which also
fulfills standard applications. This is the reason that within the MICROMASTER
series of drive units, BICO technology ( flexibility) and fast parameterization
using parameters P0700 / P1000 ( usability) or P0719 ( combination
P0700/P1000) have been introduced to be able to fulfill both of these requirements.
3.1.2.1 Selecting the command source P0700 / selecting the setpoint
source P1000
The following parameters can be used to quickly interconnect setpoints and control
signals:
¾ P0700 "Selection of command source"
¾ P1000 "Selection of setpoint source"
These parameters are used to define via which interface the drive inverter receives
the setpoint or the power-on/power-off command. The interfaces, listed in Table
3-2 can be selected for the command source P0700.
Table 3-2 Parameter P0700
Parameter values Significance / command source
0
Factory default
1
BOP (operator panel, refer to Section 3.2.1)
2
Terminal strip
4
USS on BOP link
5
USS on COM link
6
CB on COM link
The following internal or external sources / interfaces can be selected for the
frequency setpoint source P1000. In addition to the main setpoint (1
st
position), a
supplementary setpoint (2
nd
position) can be selected (refer to Table 3-3).

Table of Contents

Other manuals for Siemens MICROMASTER 440

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MICROMASTER 440 and is the answer not in the manual?

Siemens MICROMASTER 440 Specifications

General IconGeneral
Power Range0.12 kW to 250 kW
Output Voltage0 V to Input Voltage
Output Frequency0 Hz to 650 Hz
Control ModesVector control
Overload Capability150% for 60 seconds
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesPROFIBUS, DeviceNet, CANopen, Modbus RTU
Enclosure RatingIP20
Ambient Temperature-10°C to +50°C
Input Voltage200 V to 240 V (±10%), 380 V to 480 V (±10%)