Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
152 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
No.
Designation
Unit
Information
104
2)
Max. current I_max_10mA
10 mA
105
2)
Current I_L1_10mA 10 mA
106
2)
Current I_L2_10mA
10 mA
107
2)
Current I_L3_10mA 10 mA
108
2)
Max. current I_max_100mA
100 mA
109
2)
Current I_L1_100mA
100 mA
110
2)
Current I_L2_100mA
100 mA
111
2)
Current I_L3_100mA
100 mA
...
255
Reserved
1) S7 format: 0/4mA=0; 20mA=27648
2) For SIMOCODE pro S only
Table 3- 21 Socket assignment table - analog in float format
No.
Designation
Unit
Info
0
Not connected
BU0 BU1 BU2(+)
1
Reserved
2
Reserved
3
Reserved
4
Current I_max_A_F
1 A
UM+
5
Current I_avg_A_F
1 A
UM+
6
Current I_L1_A_F
1 A
UM+
7
Current I_L2_A_F
1 A
UM+
8
Current I_L3_A_F
1 A
UM+
9
Active power P_F
1 W
UM+
10
Apparent power S_F
1 VA
UM+
11
Voltage UL1_F
1 V
UM+
12 Voltage UL2_F 1 V UM+
13
Voltage UL3_F
1 V
UM+
14 Cos phi_F 1 % UM+
15
Frequency_F
1 Hz
UM+
16
Reserved
...
Reserved
255
Reserved

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals