3.4.2.18
Data record 165 - Identification
You can access the following identifiers stored in the device:
Plant identifier
Location designation
Installation date
Comment.
Table 3- 69 Data record 165 - Identification
Byte.Bit
Designation
Type
Information
0.0
Reserved
Byte[4]
4.0
Plant identifier
Byte[32]
36.0
Location designation
Byte[22]
58.0 Date Byte[16]
74.0
Reserved
Byte[38]
112.0
Comment
Byte[54]
3.4.2.19
Data record 224 - Password protection
Description
Password protection ON
If the data record is received with this control flag, the password protection is activated
and the password applied. If "Password protection on" and the password are not identical
at the time of receipt, the event "Event - Wrong password" is set and no change will be
made.
Password protection OFF
If the data record is received with this control flag, the password protection is deactivated.
If the password is incorrect, the event "Event - Wrong password" is set and no change is
made.
Table 3- 70 Data record 224 - Password protection
Byte.Bit
Designation
Type
Information
0.0
Reserved
Byte[4]
4.0 Control flag:
0 = Password protection off, 1 = Password protection on
Bit
4.1
Reserved
Bit[31]
8.0
Password
Byte[8]
16.0
Reserved
Byte[8]

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals