EasyManuals Logo
Home>Siemens>Control Unit>SIMOCODE pro

Siemens SIMOCODE pro Function Manual

Siemens SIMOCODE pro
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #273 background imageLoading...
Page #273 background image
Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
273
3.4.2.17
Data record 140 - Marking 2
For limit monitors, and monitoring functions of the temperature and analog modules, user-
specific texts can be configured for marking.
You can access the following texts via data record 140:
Limit 5 and 6
TM2 warnings T> / trip T>
AM2 warning / trip 0/4-20mA<>.
Note
Changing the marking
Each change to the marking requires that the communication interfac
e be restarted when
the web server is active. A new start interrupts all Ethernet and PROFINET links and
reestablishes them afterward.
Table 3- 68 Data record 140 - Marking 2
Byte.Bit
Designation
Type
Information
0.0 Coordination Byte[4]
4.0
Reserved
10.0
Marking limit 5
Byte[10]
20.0
Marking limit 6
Byte[10]
30.0
Marking - TM2 warning T>
Byte[10]
40.0
Marking - TM2 trip T>
Byte[10]
50.0
Marking - Warning 0/4-20 mA>
Byte[10]
60.0
Marking - Warning 0/4-20 mA<
Byte[10]
70.0
Marking - Trip 0/4-20 mA>
Byte[10]
80.0
Marking - Trip 0/4-20 mA>
Byte[10]
90.0
Reserved
Byte[110]

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals