EasyManuals Logo
Home>Siemens>Control Unit>SIMOCODE pro

Siemens SIMOCODE pro Function Manual

Siemens SIMOCODE pro
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #279 background imageLoading...
Page #279 background image
Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
279
3.5.2.3
Measured values
Table 3- 74 Measured values
Input/holding register
Designation
Type
Range
Unit
Access
5)
Info
Address offset
high/low
0x0800
Reserved
Byte[2]
r
0x0801
Reserved
Byte[2]
r
0x0802
high
Thermal motor model
Byte
0 - 255
See
2)
r
low
Phase unbalance
Byte
0 - 100
1 %
r
0x0803
high
Cos phi
Byte
0 - 100
1 %
r
low
Reserved
Byte[1]
r
0x0804
Reserved
Byte[2]
r
0x0805
Reserved
Byte[2]
r
0x0806
Max. current I_max
Word
0 - 65535
1 % / I
s
r
0x0807
Current I_L1
Word
0 - 65535
1 % / I
s
r
0x0808
Current I_L2
Word
0 - 65535
1 % / I
s
r
0x0809
Current I_L3
Word
0 - 65535
1 % / I
s
r
0x080A
Last trip current
Word
0 - 65535
1 % / I
s
r
0x080B
Time to trip
Word
0 - 65535
100 ms
r
0x080C
Cooling down period
Word
0 - 65535
100 ms
r
0x080D
Voltage U_L1
Word
0 - 65535
1 V
r
0x080E
Voltage U_L2
Word
0 - 65535
1 V
r
0x080F
Voltage U_L3
Word
0 - 65535
1 V
r
0x0810
AM1 - output
Word
0 - 32767
See
1)
r
0x0811
AM1 - input 1
Word
0 - 32767
r
0x0812
AM1 - input 2
Word
0 - 32767
r
0x0813
Reserved
Word
0 - 32767
r
0x0814
TM1 - Temperature
Word
0 - 65535
1 K see
3)
r
0x0815
TM1 - temperature 1
Word
0 - 65535
r
0x0816
TM1 - temperature 2
Word
0 - 65535
r
0x0817 TM1 - temperature 3 Word 0 - 65535 r
0x0818
EM+
4)
- ground-fault current
Word
0 - 65535
r
0x0819
EM+
4)
- last tripping current
Word
0 - 65535
r
0x081A
Active power P
D-word
0 - 0xFFFFFFFF
1 W
r
0x081C
Apparent power S
D word
0 - 0xFFFFFFFF
1 VA
r
0x0842
Frequency
Word
0 - 65535
0.01 Hz
r
from E03
0x0848
Current I_max_A_F
Float
1 A
r
from E03
0x084A
Current I_avg_A_F
Float
1 A
r
from E03
0x084C
Current I_L1_A_F
Float
1 A
r
from E03
0x084E
Current I_L2_A_F
Float
1 A
r
from E03
0x0850
Current I_L3_A_F
Float
1 A
r
from E03
0x0852
Active power P_F
Float
1 W
r
from E03
0x0854
Apparent power S
Float
1 VA
r
from E03

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals