Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
280 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Input/holding register
Designation
Type
Range
Unit
Access
5)
Info
Address offset
high/low
0x0856
Voltage UL1_F
Float
1 V
r
from E03
0x0858
Voltage UL2_F
Float
1 V
r
from E03
0x085A Voltage UL3_F Float 1 V r from E03
0x085C
Cos phi_F
Float
r
from E03
0x085E
Frequency_F
Float
1 Hz
r
from E03
1) S7 format: 0/4 mA = 0; 20 mA = 27648
2) Representation of the "Thermal motor model": Value related to symmetrical trip level,
representation in steps of 2 % in bits 6 ...0 (range 0 to 254 %), bit 7 shows unbalance (fixed
level 50 %)
3) Representation in Kelvin
4) 3UF7510-1AA00-0 ground-fault module
5) r/w: Value is read/write; r: Value is read-only