EasyManuals Logo
Home>Siemens>Control Unit>SIMOCODE pro

Siemens SIMOCODE pro Function Manual

Siemens SIMOCODE pro
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #181 background imageLoading...
Page #181 background image
Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
181
3.3.2.12
Data record 131 - Basic device parameters 2 (plug binary)
Table 3- 34 Data record 131 - Basic device parameters 2
Byte.Bit
Designation (PRM group)
Type
Range
Default
Note
Information
0.0
Reserved
Byte[4]
4.0
Byte parameters (40)
4.0
BU - Output 1
Byte
0 - 255
0
BU0 BU1 BU2(+)
5.0 BU - Output 2 Byte 0 - 255 0 BU0 BU1 BU2(+)
6.0
BU - Output 3
Byte
0 - 255
0
BU1 BU2(+)
7.0
Reserved
Byte
0
8.0
OP - LED green 1
Byte
0 - 255
0
OP OPD
9.0
OP - LED green 2
Byte
0 - 255
0
OP OPD
10.0
OP - LED green 3
Byte
0 - 255
0
OP OPD
11.0
OP - LED green 4
Byte
0 - 255
0
OP OPD
12.0
OP - LED yellow 1
Byte
0 - 255
0
OP
13.0
OP - LED yellow 2
Byte
0 - 255
0
OP
14.0
OP - LED yellow 3
Byte
0 - 255
0
OP
15.0
Reserved
Byte
0
16.0 Cyclic send - Bit 0.0 Byte 0 - 255 105 Default: Status
- ON<
BU0 BU1 BU2(+)
17.0 Cyclic send - Bit 0.1 Byte 0 - 255 106 Default: Status
- Off
BU0 BU1 BU2(+)
18.0 Cyclic send - Bit 0.2 Byte 0 - 255 107
Default: Status
- ON>
BU0 BU1 BU2(+)
19.0 Cyclic send - Bit 0.3 Byte 0 - 255 128 Default: Event
- Overload
operation
BU0 BU1 BU2(+)
20.0 Cyclic send - Bit 0.4 Byte 0 - 255 110 Default: Status
- Interlocking
time active
BU0 BU1 BU2(+)
21.0 Cyclic send - Bit 0.5 Byte 0 - 255 120
Default: Status
- Auto mode
BU0 BU1 BU2(+)
22.0 Cyclic send - Bit 0.6 Byte 0 - 255 96
Default: Status
- General fault
BU0 BU1 BU2(+)
23.0 Cyclic send - Bit 0.7 Byte 0 - 255 97 Default: Status
- group
warning
BU0 BU1 BU2(+)
24.0
Cyclic send - Bit 1.0
Byte
0 - 255
0
BU0 BU1 BU2(+)
25.0
Cyclic send - Bit 1.1
Byte
0 - 255
0
BU0 BU1 BU2(+)
26.0
Cyclic send - Bit 1.2
Byte
0 - 255
0
BU0 BU1 BU2(+)
27.0
Cyclic send - Bit 1.3
Byte
0 - 255
0
BU0 BU1 BU2(+)
28.0
Cyclic send - Bit 1.4
Byte
0 - 255
0
BU0 BU1 BU2(+)
29.0
Cyclic send - Bit 1.5
Byte
0 - 255
0
BU0 BU1 BU2(+)
30.0
Cyclic send - Bit 1.6
Byte
0 - 255
0
BU0 BU1 BU2(+)
31.0
Cyclic send - Bit 1.7
Byte
0 - 255
0
BU0 BU1 BU2(+)

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals