Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
180 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
50.0 Truth table 3 type 3I/1O Byte 0 -
1111111
0 BU0 BU1 BU2(+)
51.0
Reserved
Byte
0
52.0 Motor protection - Cooling
Word 600 -
100 ms 3000
IM / UM(+)
54.0 Motor protection - Pause
Word 0 -
100 ms 0 0 = disabled
IM / UM(+)
56.0 Execution time Word 0 -
65535
100 ms 10 0 = disabled
BU0 BU1 BU2(+)
58.0 Monitoring the number of
starts - Time range for
Word 0 -
65535
1 s 0
BU0 BU1 BU2(+)
60.0 Monitoring the number of
starts - Interlocking time
Word 0 -
65535
1 s 0
BU0 BU1 BU2(+)
62.0 Motor stop time level > Word 0 -
65535
1 h 0
BU0 BU1 BU2(+)
64.0 Timer 1 - Limit Word 0 -
65535
100 ms 0
BU0 BU1 BU2(+)
66.0 Timer 2 - Limit Word 0 -
65535
100 ms 0
BU0 BU1 BU2(+)
68.0 Counter 1 - Limit Word 0 -
65535
0
BU0 BU1 BU2(+)
70.0 Counter 2 - Limit Word 0 -
65535
0
BU0 BU1 BU2(+)
72.0 EM+
2)
- trip level Word 30 -
40000
1 mA 1000 BU0 BU2(+)
74.0 EM+
2)
- warning level Word 30 -
1 mA 500 BU0 BU2(+)
76.0 Operator control enable Bit
0 ...
0..0B
80.0 Motor protection - set
D-
1)
10 mA 30
IM / UM(+)
84.0 Motor operating hours
level >
D-
word
0 -
0xFFFF
1 s 0
BU0 BU1 BU2(+)
88.0
Reserved
D-
0
1) Value range dependent on current range of the IM / UM and the conversion factor;
bit 31 = 1, i.e. conversion factor is active
2) 3UF7510-1AA00-0 ground-fault module
3) Class 7 only for BU2+