Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
173
Byte.Bit
Designation
Type
Range
Unit
Information
168.0
Apparent power S_F
Float
1 VA
UM+
172.0 Voltage U1_F Float 1 V UM+
176.0
Voltage U2_F
Float
1 V
UM+
180.0 Voltage U3_F Float 1 V UM+
184.0
Cos phi_F
Float
UM+
188.0
Frequency_F
Float
1 Hz
UM+
192.0
Reserved
Byte[8]
1) S7 format:
0/4 mA = 0
20 mA = 27648
2) Representation of the "Thermal motor model":
Value always refers to symm. trip level,
representation in 2 % increments in bits 6 - 0 (range 0 to 254 %), bit 7 shows unbalance
(fixed level 50 %).
3) Representation in Kelvin.
4) 3UF7510-1AA00-0 ground-fault module