EasyManuals Logo
Home>Siemens>Control Unit>SIMOCODE pro

Siemens SIMOCODE pro Function Manual

Siemens SIMOCODE pro
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
Communication
2.2 PROFINET communication
SIMOCODE pro - Communication
76 Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Example of the diagnostics data records
The following example shows the content of the data record 0xC010 with the pending fault
"execution of ON command":
Table 2- 27 Content of data record 0xC010 for the pending fault "execution ON command"
BlockType
0x0010: Diagnostics data record
BlockLength
0x0016: Block length 22 bytes
BlockVersion
0x0101: always 0x0101 in the case of SIMOCODE
API
0x00000000: always 0 in the case of SIMOCODE
SlotNumber 0x0001: Slot 1 - I/O address
SubslotNumber
0x0001: Sub-slot 1
ChannelNumber
0x8000: Submodule
ChannelProperties
0x0800: Pending diagnostics
USI (User Structure Identifier)
0x8000: Channel diagnostics
ChannelNumber
0x0000: always 0 in the case of SIMOCODE
ChannelProperties
0x6804: Pending diagnostics
ChannelErrorType
0x1000: Execution ON command

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals