SIMOCODE pro response tables
Specific responses (deactivated, signaling, warning, tripping) can be parameterized for
various SIMOCODE pro functions, such as overload. These are always displayed in tabular
form:
● "X" = Applicable
● "—" = Not applicable
● Default values are marked "d" for "default" in parentheses.
Warning X (d) X —
Deactivated X X X (d)
0 ... 25.5 s (default: 0)
Brief description of the responses:
● Tripping: The contactor controls QE* are tripped. A fault message is generated which is
available as a diagnosis via PROFIBUS DP. The fault message and the device-internal
signal remain on until the appropriate length of time has elapsed or the cause of the fault
has been eliminated and acknowledged.
● Warning: In addition to the device-internal signal, a warning signal is generated that is
available as diagnostics via the communication bus.
● Signaling: Only a device-internal signal is generated, which can be further processed as
required.
● Deactivated: The appropriate function is switched off, no signals are generated.
A delay time can also be set for specific responses.