4.10.11.3 Installing the GSD
Procedure
1. Save the GSD on your PC using one of the following methods.
– With Internet access:
GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100)
– Without Internet access:
Insert a memory card into the converter.
Set p0804 =12.
The converter writes the GSD as zipped le (*.zip) into directory /SIEMENS/SINAMICS/
DATA/CFG on the memory card.
2. Unzip the GSD le on your computer.
3. Import the GSD in the engineering system of the controller.
You have now installed the GSD le in the engineering system of the controller.
4.10.11.4 Set the PROFIBUS address
Valid address area: 1 … 125
You have the following options for setting the address:
• Using the address switch on the Control Unit:
([DPSOH
2II
%LW
%LW
%LW
%LW
%LW
%LW
%LW
2II2Q2Q
Figure4-46 Address switch with example for bus address 10
The address switch has priority over the other settings.
• With a commissioning tool, e.g. an operator panel, via parameter p0918 (factory setting:
p0918=126).
It is only possible to change p0918 if an invalid address is set in the address switch.
Overview of the interfaces (Page82)
Installing
4.10Connecting the interfaces for the converter control
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 115