Application class Standard Drive Control Dynamic Drive Control
Max. output fre‐
quency
550Hz 240Hz
Commissioning
• Unlike "Dynamic Drive Control," no speed con‐
troller needs to be set
• When compared to "Expert":
– Simplied commissioning using prede‐
ned motor data
– Reduced number of parameters
• "Standard Drive Control" is preset for convert‐
ers frame size A… frame sizeC
• Fewer number of parameters when compared to
setting "Expert"
• "Dynamic Drive Control" is preset for converters
frame size D… frame sizeF
5.4.4 Standard Drive Control
Function description
Select the motor standard:
•
: IEC
• : NEMA, US units
• : NEMA, SI units
Set the converter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
• : Third-party induction motor
• : 1LE1, 1LG6, 1LA7, 1LA9 induction motors
Motors with motor code stamped on the rating plate:
• : 1LE1.9
• : 1PC1
• : Induction motor
Depending on the converter, the motor list in BOP‑2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The
converter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code=0, and enter motor
data from p0304 and higher from the rating plate.
87Hz motor operation The BOP‑2 only indicates this step if you selected IEC as the motor
standard (EUR/USA, P100 = kW 50Hz).