11.3 Overload capability of the converter
Overload capability is the property of the converter to temporarily supply a current that is higher
than the rated current to accelerate a load. Two typical load cycles are de󹪝ned to clearly
demonstrate the overload capability: "Low Overload" and "High Overload"
De󹪝nitions
Base load
Constant load between the accelerating phases of the drive
Low Overload High Overload
LO base load input current
Permissible input current for a "Low Over‐
load" load cycle
LO base load output current
Permissible output current for a "Low
Overload" load cycle
LO base load power
Rated power based on the LO base load
output current
HO base load input current
Permissible input current for a "High
Overload" load cycle
HO base load output current
Permissible output current for a "High
Overload" load cycle
HO base load power
Rated power based on the HO base load
output current
If not speci󹪝ed otherwise, the power and current data in the technical data always refer to a
load cycle according to Low Overload.
We recommend using the "SIZER" engineering software to select the converter.
You can 󹪝nd additional information about SIZER on the Internet:
Download SIZER (http://support.automation.siemens.com/WW/view/en/
10804987/130000)
Load cycles and typical applications:
"Low Overload" load cycle "High Overload" load cycle
The "Low Overload" load cycle assumes a
uniform base load with low requirements
placed on brief accelerating phases. Typical
applications when designing according to
"Low Overload" include:
Pumps, fans and compressors
Wet or dry blasting technology
Mills, mixers, kneaders, crushers, agita‐
tors
Basic spindles
Rotary furnaces
Extruders
The "High Overload" load cycle permits dy‐
namic accelerating phases at a reduced base
load. Typical applications when designing
according to "High Overload" include:
Horizontal and vertical conveyor technol‐
ogy (conveyor belts, roller conveyors,
chain conveyors)
Centrifuges
Escalators/moving stairways
Lifters/Lowerers
Elevators
Gantry cranes
Cable railways
Storage and retrieval machines
Technical data
11.3Overload capability of the converter
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 423

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G120C
CategoryInverter
LanguageEnglish

Related product manuals