8.4.8 Analog output
Function description
$2
&2U[[\\
S
S>@
Dene the analog output type
Dene the analog output type using parameter p0776.
Current output (factory setting) 0mA…+20mA p0776[0]= 0
Voltage output 0V…+10V 1
Current output +4mA…+20mA 2
Dening the analog output function
You dene the analog output function by interconnecting parameter p0771 with a connector
output of your choice. Parameter p0771 is assigned to the specic analog output via its
index, e.g. parameter p0771[0] is assigned to analog output0.
Connector outputs are marked with "CO" in the parameter list of the List Manual.
Interconnecting signals in the converter (Page461)
Example
To output the converter output current via analog output0, you must interconnect AO0 with
the signal for the output current.
Set p0771=27.
Dening the function of an analog output
Table 8-5 Frequently used connector outputs (CO) of the converter
Parameter Description Factory setting
r0021 CO: Speed actual value, smoothed - rpm
r0025 CO: Output voltage, smoothed - Vrms
r0026 CO: DC link voltage, smoothed - V
r0027 CO: Absolute actual current, smoothed - Arms
r0063 CO: Speed actual value - rpm
You can nd additional connector outputs in the parameter list.
Overview of the manuals (Page465)
Advanced commissioning
8.4Adapt the default setting of the terminal strip
SINAMICS G120C Converters
198 Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK