A.1.5 Firmware version 4.7 SP6
Table A-5 New functions and function changes in rmware4.7 SP6
Function SINAMICS
G120 G120D
1
Support for the Power Module PM240-2, FSF frame sizes - - ✓ ✓ ✓ ✓ - - -
Support of PM240P‑2 Power Modules frame sizes FSD…FSF - - ✓ ✓ ✓ - - - -
Support of safety function Safe Torque O (STO) via the terminals of the
PM240‑2 Power Module, frame size FSF and PM240P‑2Power Module
FSD…FSF
- - - - ✓ ✓ - - -
2 Support for Power Module PM330 JX frame size - - ✓ - - - - - -
3 Support for 1PC1 induction motors ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
4 The control of synchronous reluctance takes into account the inductance of
the output reactor.
- - ✓ - - - - - -
5 Support of motor temperature sensor Pt1000 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
6 New p4621 parameter for disabling PTC short-circuit monitoring - - - - - - ✓ ✓ ✓
7 Revision of the thermal motor model for protecting the motor against dam‐
age due to overheating in the stator or rotor
✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
8 Changing the quick commissioning in the "Standard Drive Control" applica‐
tion class:
The motor data identication is no longer permanently set to p1900=12;
instead, users select the appropriate motor data identication.
Factory setting: p1900=2.
- ✓ ✓ ✓ ✓ ✓ - - -
9 The free function blocks are also available in the SINAMICS G120C. ✓ ✓ ✓ ✓ ✓ ✓ ✓ - -
Appendix
A.1New and extended functions
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 455