EasyManuals Logo

Siemens SINAMICS G120C User Manual

Siemens SINAMICS G120C
478 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #179 background imageLoading...
Page #179 background image
Function description
The active know-how protection provides the following:
With just a few exceptions, the values of all adjustable parameters p… are invisible.
Several adjustable parameters can be read and changed when know-how protection is
active.
In addition, you can de󹪝ne an exception list of adjustable parameters, which end users
may change.
Several adjustable parameters can be read but not changed when know-how protection
is active.
The values of monitoring parameters r… remain visible.
Locked functions:
Downloading converter settings using a PC
Automatic controller optimization
Stationary or rotating measurement of the motor data identi󹪝cation
Deleting the alarm history and the fault history
Generating acceptance documents for safety functions
Executable functions:
Restoring factory settings
Acknowledging faults
Displaying faults, alarms, fault history, and alarm history
Reading out the diagnostic bu󹪜er
Controlling a converter using a PC
Uploading adjustable parameters that can be changed or read when know-how
protection is active.
Displaying acceptance documents for safety functions
When know-how protection is active, support can only be provided (from Technical Support)
after prior agreement from the machine manufacturer (OEM).
Know-how protection without copy protection
You can transfer the converter settings to another converter, e.g. using a memory card or an
operator panel.
Know-how protection with basic copy protection
After replacing a converter, to be able to operate the new converter with the settings of the
replaced converter without knowing the password, the memory card must be inserted in the
new converter.
Know-how protection with extended copy protection
It is not possible to insert and use the memory card in another converter without knowing
the password.
Protecting the converter settings
7.2Know-how protection
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK 177

Table of Contents

Other manuals for Siemens SINAMICS G120C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120C and is the answer not in the manual?

Siemens SINAMICS G120C Specifications

General IconGeneral
Communication InterfacesPROFINET, PROFIBUS, USS, Modbus RTU
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Power Range0.55 kW to 132 kW
Voltage Range380 V to 480 V
Output Voltage0 V to Supply Voltage
Frequency Range0 Hz to rated output frequency
Control ModesVector control with encoder
ProtectionOverload, overvoltage, undervoltage, short circuit, ground fault
Relative Humidity5% to 95%, non-condensing
AltitudeUp to 2000 m without derating

Related product manuals